Discussion on short-circuit current breaking capacity of low-voltage side circuit breakers of distribution transformers

×
Discussion on short-circuit current breaking capacity of low-voltage side circuit breakers of distribution transformers

Since the data of the system short-circuit capacity and short-circuit impedance need to be provided by the power supply department, the electrical design of most civil construction projects does not make accurate short-circuit current calculations at present.

Correct method: Calculate the short-circuit current of the low-voltage side for the transformers of different capacities of each project, including at least the peak value of the short-circuit current: ip

Steady State Short-Circuit Current RMS: Ik

When choosing a circuit breaker, at least the rated ultimate short-circuit breaking capacity of the circuit breaker should be guaranteed: Icu

Not less than: Ik

For each project, a cable with the smallest cross-sectional area and a short path should be selected for short-circuit current thermal stability verification, and a load terminal with the longest distribution path should be selected for voltage drop analysis. If the cable cross-sectional area does not meet the requirements, the cable cross-sectional area should be adjusted.

Under the condition that the system capacity is infinite, the circuit current parameters at the outlet of the low-voltage side of the transformer corresponding to different capacity and short-circuit impedance voltage parameters must be greater than the short-circuit capacity of the actual project whose short-circuit capacity of the system is not infinite. It can be used to check the low-voltage distribution. The breaking capacity of the electrical circuit breaker.

For another example, it can be seen from the selection table for short-circuit current of low-voltage copper core XLPE cables that for transformers of 1000kVA and below, the cross-sectional area of the distribution cable on the low-voltage bus shall not be less than 10mm2; for transformers greater than 1000kVA, the The cross-sectional area of the distribution cable shall not be less than 16mm2.

For large-scale or important public construction projects, short-circuit current calculation is recommended when short-circuit current has a great influence on equipment selection.

prev
Intro to CANWIN The third-generation transformer core processing center was put into production as planned Canwin
Power Transformer Equipment PrecisionCut / High speed spacer slitting line Ready to Ship- Made by Canwin China
next
recommended for you
Get in touch with us
Specializing in the research and development of Silicon Steel Sheet Cut to Length Lines, power transformers, Silicon Steel Sheet Slitting Lines, and Transformer Foil Winding Machines, the company operates with a strong emphasis on innovation and precision engineering.
Contact us
Contact Sales at Ms. Flora Lu
Mobile:+86 1370-228-2846
Tel: (+86) 750-887-3161
Fax: (+86) 750-887-3199
E-mail: info@canwinsg.com
Office add: No.1 Pankeng Road, Gonghe Town, Heshan, Jiangmen, GD, China 529700
Singapore office add: 10, Bukit Batok Crescent, #04-04, The Spire, Singapore 658079
Copyright © 2026 CANWIN | Sitemap
Customer service
detect